什么是配電系統?

發布時(shi)間:作者:cobinet 萬兆(zhao)屏蔽模塊瀏覽:494次來源:數據中(zhong)心運維管(guan)理
CobiNet(寧波)推薦文章:

傳統(tong)上將(jiang)電力系統(tong)劃分為(wei)發電、輸電和配電三大組成系統(tong)。

發電(dian)(dian)系(xi)統發出(chu)(chu)的(de)電(dian)(dian)能經由輸電(dian)(dian)系(xi)統的(de)輸送(song),最后(hou)由配電(dian)(dian)系(xi)統分(fen)配給各個(ge)用戶(hu)。一般地,將(jiang)電(dian)(dian)力系(xi)統中從降壓(ya)(ya)配電(dian)(dian)變(bian)電(dian)(dian)站(zhan)(高壓(ya)(ya)配電(dian)(dian)變(bian)電(dian)(dian)站(zhan))出(chu)(chu)口(kou)到(dao)用戶(hu)端(duan)的(de)這一段系(xi)統稱為配電(dian)(dian)系(xi)統。

配(pei)(pei)電(dian)(dian)系統是由(you)多種配(pei)(pei)電(dian)(dian)設備(或(huo)元件)和配(pei)(pei)電(dian)(dian)設施所組成(cheng)的變換電(dian)(dian)壓和直接向終端用戶分配(pei)(pei)電(dian)(dian)能的一個電(dian)(dian)力網(wang)絡系統。

配電系統的組成

在(zai)我國,配(pei)(pei)(pei)(pei)電(dian)(dian)(dian)系(xi)(xi)(xi)統(tong)(tong)可劃分(fen)為高壓(ya)配(pei)(pei)(pei)(pei)電(dian)(dian)(dian)系(xi)(xi)(xi)統(tong)(tong)、中壓(ya)配(pei)(pei)(pei)(pei)電(dian)(dian)(dian)系(xi)(xi)(xi)統(tong)(tong)和(he)低壓(ya)配(pei)(pei)(pei)(pei)電(dian)(dian)(dian)系(xi)(xi)(xi)統(tong)(tong)三部分(fen)。由于配(pei)(pei)(pei)(pei)電(dian)(dian)(dian)系(xi)(xi)(xi)統(tong)(tong)作為電(dian)(dian)(dian)力系(xi)(xi)(xi)統(tong)(tong)的最后一(yi)個環節直(zhi)接面向終端用(yong)戶,它的完善與否直(zhi)接關系(xi)(xi)(xi)著廣(guang)大用(yong)戶的用(yong)電(dian)(dian)(dian)可靠性和(he)用(yong)電(dian)(dian)(dian)質(zhi)量,因而在(zai)電(dian)(dian)(dian)力系(xi)(xi)(xi)統(tong)(tong)中具有重要的地位。

我國配(pei)電(dian)(dian)系(xi)統的電(dian)(dian)壓(ya)(ya)等(deng)級,根據《城市電(dian)(dian)網規(gui)劃設(she)計導則》的規(gui)定,220kV及其以上(shang)電(dian)(dian)壓(ya)(ya)為輸(shu)變電(dian)(dian)系(xi)統,35、63、110kV為高壓(ya)(ya)配(pei)電(dian)(dian)系(xi)統,10、6kV為中壓(ya)(ya)配(pei)電(dian)(dian)系(xi)統,380、220V為低壓(ya)(ya)配(pei)電(dian)(dian)系(xi)統。

配電(dian)系(xi)統變(bian)壓器異常運行方式

變壓器的安(an)全運(yun)行管(guan)理(li)工作(zuo)是我們日常(chang)工作(zuo)的重點,通過對變壓器的異常(chang)運(yun)行情況、常(chang)見故障分析的經驗總(zong)結,將有利于(yu)及時、準(zhun)確判(pan)斷故障原因、性質(zhi),及時采(cai)取有效措施(shi),確保(bao)設備的安(an)全運(yun)行。

變(bian)壓器(qi)是輸配(pei)電系統中極(ji)其重要(yao)的電器(qi)設備(bei),根據(ju)運(yun)行維(wei)護管理(li)規定(ding)變(bian)壓器(qi)必須定(ding)期進(jin)行檢(jian)查,以(yi)便(bian)及時了(le)解和掌握(wo)變(bian)壓器(qi)的運(yun)行情(qing)況,及時采取有(you)效措施(shi),力爭把故障消除在(zai)萌芽狀(zhuang)態之中,從而保障變(bian)壓器(qi)的安(an)全運(yun)行。

變壓器異常運行和常見(jian)故(gu)障(zhang)如下

一、變壓器(qi)聲音出(chu)現異(yi)常的情況。

二、在正(zheng)常(chang)負(fu)荷和正(zheng)常(chang)冷卻方式下(xia),變壓器出現油溫不斷升高的情況(kuang)。

三(san)、變(bian)壓(ya)器絕(jue)緣油顏色出(chu)現(xian)顯著(zhu)變(bian)化的情況(kuang)。

四、油枕(zhen)或防爆管出現噴油的情況。

五、出(chu)現三(san)相(xiang)電(dian)壓(ya)不平衡的情況。

六、繼電保護發生動作的情況(kuang)。

七、絕(jue)緣瓷(ci)套管(guan)出現閃絡和(he)爆炸的情況(kuang)。

八(ba)、分接開(kai)關出現故障的情(qing)況。

低壓配電系統(tong)的基本方式(shi)

根據IEC規(gui)定(ding)的各種保(bao)護方(fang)式、術語概念,低(di)壓配電(dian)系(xi)統按接地方(fang)式的不(bu)同(tong)分為三類,即TT、TN和(he)IT系(xi)統,分述如下。

1、TT方(fang)式(shi)供電(dian)系(xi)統(tong)TT方(fang)式(shi)是指將電(dian)氣設備的(de)金屬外(wai)殼直(zhi)接(jie)(jie)接(jie)(jie)地的(de)保(bao)護系(xi)統(tong),稱為保(bao)護接(jie)(jie)地系(xi)統(tong),也(ye)稱TT系(xi)統(tong)。第一個(ge)符號(hao)T表示(shi)電(dian)力系(xi)統(tong)中(zhong)(zhong)性點直(zhi)接(jie)(jie)接(jie)(jie)地;第二個(ge)符號(hao)T表示(shi)負(fu)載設備外(wai)露不與(yu)帶電(dian)體相接(jie)(jie)的(de)金屬導電(dian)部分(fen)與(yu)大地直(zhi)接(jie)(jie)聯接(jie)(jie),而與(yu)系(xi)統(tong)如(ru)何接(jie)(jie)地無(wu)關。在TT系(xi)統(tong)中(zhong)(zhong)負(fu)載的(de)所有接(jie)(jie)地均(jun)稱為保(bao)護接(jie)(jie)地,這種供電(dian)系(xi)統(tong)的(de)特點如(ru)下(xia)。

(1)當電(dian)氣設備的金屬外(wai)殼帶電(dian)(相線碰殼或設備絕緣(yuan)損(sun)壞而漏(lou)電(dian))時,由于有(you)接地保護,可(ke)以大大減少觸電(dian)的危險性(xing)。但是,低壓(ya)斷路器(自(zi)動開關)不一定能跳閘,造成漏(lou)電(dian)設備的外(wai)殼對地電(dian)壓(ya)高于安全電(dian)壓(ya),屬于危險電(dian)壓(ya)。

(2)當漏電(dian)電(dian)流(liu)比較小(xiao)時,即使有熔斷器也不(bu)一定能熔斷,所以(yi)(yi)還需要漏電(dian)保護器作(zuo)保護,困此(ci)TT系統難以(yi)(yi)推廣。

(3)TT系統接地(di)裝置耗用鋼材多,而且難以回收、費工(gong)時、費料。

現在有的建筑單位(wei)(wei)是采用(yong)(yong)TT系(xi)統,施工單位(wei)(wei)借(jie)用(yong)(yong)其(qi)電源(yuan)作臨時用(yong)(yong)電時,應用(yong)(yong)一條專用(yong)(yong)保護線,以減少需接地(di)裝置鋼材用(yong)(yong)量。

把新增加的專(zhuan)用(yong)(yong)(yong)保護(hu)線(xian)(xian)PE線(xian)(xian)和工作(zuo)零(ling)線(xian)(xian)N分(fen)開,其特點是:①共(gong)用(yong)(yong)(yong)接地(di)線(xian)(xian)與工作(zuo)零(ling)線(xian)(xian)沒有(you)電(dian)(dian)的聯系;②正常運(yun)行時,工作(zuo)零(ling)線(xian)(xian)可(ke)以有(you)電(dian)(dian)流,而(er)專(zhuan)用(yong)(yong)(yong)保護(hu)線(xian)(xian)沒有(you)電(dian)(dian)流;③TT系統適用(yong)(yong)(yong)于(yu)接地(di)保護(hu)占很分(fen)散的地(di)方。

2、TN方式供電(dian)系(xi)(xi)統這種供電(dian)系(xi)(xi)統是(shi)將電(dian)氣設備(bei)的(de)(de)金屬(shu)外(wai)殼與(yu)工(gong)作零線相接(jie)的(de)(de)保護(hu)系(xi)(xi)統,稱作接(jie)零保護(hu)系(xi)(xi)統,用(yong)TN表示(shi)。它的(de)(de)特(te)點如下。

(1)一旦(dan)設備出現外殼帶電,接零保護系統(tong)能將漏電電流(liu)(liu)上升為短路電流(liu)(liu),這個電流(liu)(liu)很大,是(shi)TT系統(tong)的(de)5.3倍(bei),實際(ji)上就是(shi)單(dan)相對地短路故障,熔(rong)(rong)斷器的(de)熔(rong)(rong)絲會(hui)熔(rong)(rong)斷,低壓斷路器的(de)脫扣器會(hui)立即動作而跳閘,使故障設備斷電,比較安全。

(2)TN系統節省材料、工(gong)時,在(zai)我國和其(qi)他許多國家(jia)廣泛得(de)到應用(yong),可見比TT系統優點多。TN方式供電(dian)系統中(zhong),根據(ju)其(qi)保護零(ling)線(xian)是(shi)否與工(gong)作零(ling)線(xian)分(fen)開而劃分(fen)為TN-C和TN-S等兩種(zhong)。

3、TN-C方式(shi)供電系統它是用工作零線兼作接零保(bao)護線,可以稱作保(bao)護中性線,可用NPE表示(shi)

4、TN-S方式供電系統(tong)(tong)它是把(ba)工(gong)作零(ling)線N和(he)專(zhuan)用(yong)保(bao)護線PE嚴格分開的供電系統(tong)(tong),稱作TN-S供電系統(tong)(tong),TN-S供電系統(tong)(tong)的特點如(ru)下(xia)。

(1)系統正常(chang)運行時,專用保(bao)護線上不有電流,只是工作零線上有不平衡電流。PE線對地沒有電壓(ya),所以電氣(qi)設備金屬外殼接零保(bao)護是接在專用的保(bao)護線PE上,安全可(ke)靠(kao)。

(2)工作零(ling)線只用作單相照明負(fu)載回路。

(3)專用保護線PE不(bu)許(xu)斷線,也不(bu)許(xu)進入漏電開關。

(4)干(gan)線(xian)上使用(yong)漏電保(bao)護(hu)器(qi),工作零(ling)線(xian)不得有(you)重復(fu)接(jie)地(di),而PE線(xian)有(you)重復(fu)接(jie)地(di),但是不經過漏電保(bao)護(hu)器(qi),所以TN-S系統供(gong)電干(gan)線(xian)上也可以安(an)裝(zhuang)漏電保(bao)護(hu)器(qi)。

(5)TN-S方式(shi)供(gong)電(dian)系(xi)統(tong)(tong)安全可靠(kao),適用(yong)(yong)于工(gong)業與(yu)民用(yong)(yong)建筑等(deng)低壓供(gong)電(dian)系(xi)統(tong)(tong)。在建筑工(gong)程工(gong)工(gong)前的 三通一平 (電(dian)通、水通、路通和(he)地平 必須采用(yong)(yong)TN-S方式(shi)供(gong)電(dian)系(xi)統(tong)(tong)。

5、TN-C-S方(fang)式(shi)供(gong)電(dian)(dian)系統(tong)在(zai)建筑施(shi)工臨時供(gong)電(dian)(dian)中,如果前(qian)部(bu)分(fen)是TN-C方(fang)式(shi)供(gong)電(dian)(dian),而施(shi)工規(gui)范(fan)規(gui)定施(shi)工現場必(bi)須采用TN-S方(fang)式(shi)供(gong)電(dian)(dian)系統(tong),則(ze)可以在(zai)系統(tong)后部(bu)分(fen)現場總(zong)配(pei)電(dian)(dian)箱分(fen)出(chu)PE線,TN-C-S系統(tong)的特點如下。

(1)工作零線(xian)N與專(zhuan)用保護線(xian)PE相聯通,如圖1-5ND這段線(xian)路不(bu)平衡電(dian)(dian)(dian)(dian)流(liu)比較大(da)(da)時,電(dian)(dian)(dian)(dian)氣設備的(de)(de)接(jie)零保護受到(dao)零線(xian)電(dian)(dian)(dian)(dian)位的(de)(de)影(ying)響。D點(dian)至后(hou)面(mian)PE線(xian)上沒有電(dian)(dian)(dian)(dian)流(liu),即該段導線(xian)上沒有電(dian)(dian)(dian)(dian)壓(ya)降,因此,TN-C-S系(xi)統可(ke)以降低電(dian)(dian)(dian)(dian)動機外(wai)(wai)殼對(dui)地(di)的(de)(de)電(dian)(dian)(dian)(dian)壓(ya),然而又不(bu)能完全消(xiao)除(chu)這個(ge)(ge)電(dian)(dian)(dian)(dian)壓(ya),這個(ge)(ge)電(dian)(dian)(dian)(dian)壓(ya)的(de)(de)大(da)(da)小取(qu)決于ND線(xian)的(de)(de)負載不(bu)平衡的(de)(de)情況及(ji)ND這段線(xian)路的(de)(de)長(chang)度。負載越不(bu)平衡,ND線(xian)又很長(chang)時,設備外(wai)(wai)殼對(dui)地(di)電(dian)(dian)(dian)(dian)壓(ya)偏(pian)移就越大(da)(da)。所以要求負載不(bu)平衡電(dian)(dian)(dian)(dian)流(liu)不(bu)能太大(da)(da),而且在PE線(xian)上應作重(zhong)復(fu)接(jie)地(di)。

(2)PE線在任何情(qing)況下都(dou)不能進入漏電(dian)保(bao)護(hu)器(qi),因為線路(lu)末端的漏電(dian)保(bao)護(hu)器(qi)動(dong)作(zuo)會使(shi)前級(ji)漏電(dian)保(bao)護(hu)器(qi)跳閘造成大(da)范圍停電(dian)。

(3)對PE線(xian)除了在(zai)總箱處必須和N線(xian)相(xiang)接以外(wai),其他各分(fen)(fen)箱處均不(bu)得把N線(xian)和PE線(xian)相(xiang)聯(lian),PE線(xian)上(shang)(shang)不(bu)許安裝(zhuang)開關和熔斷器(qi),也不(bu)得用大顧兼作(zuo)PE線(xian)。通過上(shang)(shang)述分(fen)(fen)析,TN-C-S供(gong)(gong)電(dian)系統(tong)(tong)是(shi)在(zai)TN-C系統(tong)(tong)上(shang)(shang)臨時變通的(de)作(zuo)法。當三(san)(san)相(xiang)電(dian)力變壓器(qi)工(gong)(gong)作(zuo)接地情況良(liang)好、三(san)(san)相(xiang)負(fu)載比較平衡時,TN-C-S系統(tong)(tong)在(zai)施工(gong)(gong)用電(dian)實踐中效果還是(shi)可行(xing)的(de)。但是(shi),在(zai)三(san)(san)相(xiang)負(fu)載不(bu)平衡、建筑施工(gong)(gong)工(gong)(gong)地有專用的(de)電(dian)力變壓器(qi)時,必須采(cai)用TN-S方式供(gong)(gong)電(dian)系統(tong)(tong)。

6、IT方(fang)式供電系統I表示電源側(ce)沒有工作接(jie)(jie)地,或(huo)經過高(gao)阻抗接(jie)(jie)地。第二個(ge)字母T表示負載(zai)側(ce)電氣設備進行(xing)接(jie)(jie)地保(bao)護。

IT方式(shi)供(gong)電系統(tong)在供(gong)電距(ju)離不是(shi)很長時,供(gong)電的(de)可(ke)靠性(xing)高、安全(quan)性(xing)好。一(yi)般用(yong)(yong)于(yu)不允許停(ting)電的(de)場所,或者(zhe)是(shi)要(yao)求嚴格(ge)地(di)連(lian)續供(gong)電的(de)地(di)方,例如電力煉(lian)鋼、大醫院的(de)手術(shu)室、地(di)下(xia)(xia)礦井等(deng)處。地(di)下(xia)(xia)礦井內供(gong)電條件(jian)比較差,電纜易(yi)受潮。運用(yong)(yong)IT方式(shi)供(gong)電系統(tong),即使電源(yuan)中性(xing)點不接地(di),一(yi)旦設備漏電,單相對地(di)漏電流仍小,不會破壞(huai)電源(yuan)電壓的(de)平(ping)衡,所以比電源(yuan)中性(xing)點接地(di)的(de)系統(tong)還安全(quan)。

但是,如果用在供(gong)(gong)(gong)電(dian)距(ju)離很(hen)長時,供(gong)(gong)(gong)電(dian)線路(lu)(lu)(lu)對大地的分布(bu)電(dian)容就不能(neng)忽視了。在負載發生短路(lu)(lu)(lu)故障或(huo)漏(lou)電(dian)使設備外殼帶電(dian)時,漏(lou)電(dian)電(dian)流(liu)經大地形成架路(lu)(lu)(lu),保護設備不一(yi)定動作,這是危險(xian)的。只有(you)在供(gong)(gong)(gong)電(dian)距(ju)離不太長時才比較安全(quan)。這種供(gong)(gong)(gong)電(dian)方式在工地上很(hen)少見(jian)。

配電系統節能改造

中國地區和(he)企業的(de)供配電系統,電能浪費很大,其問題是多方面的(de),主要問題及解決措(cuo)施如下(xia)述。

①電(dian)網(wang)容(rong)量與負荷不匹(pi)配

隨著經濟的(de)(de)發(fa)展和人民生活水平的(de)(de)提高(gao),用電(dian)(dian)量(liang)迅速(su)增(zeng)加(jia),原建(jian)配(pei)電(dian)(dian)網的(de)(de)設備(bei)(bei)和導線(xian)均與(yu)用電(dian)(dian)量(liang)不相(xiang)匹配(pei),不少地方超(chao)負(fu)荷運行,不僅影(ying)響供電(dian)(dian)安全,還大(da)大(da)增(zeng)加(jia)了配(pei)電(dian)(dian)系(xi)統的(de)(de)損耗。節(jie)能(neng)改造(zao)的(de)(de)辦法就是更新線(xian)路與(yu)設備(bei)(bei)。

②供電電壓不合理

有些地(di)區(qu)和許多較(jiao)大(da)型用電(dian)(dian)(dian)單位的供(gong)電(dian)(dian)(dian)電(dian)(dian)(dian)壓偏低,如過去規(gui)定企業(ye)進線電(dian)(dian)(dian)壓應(ying)為(wei)6千(qian)伏(fu),中間需(xu)經過多次(ci)降壓,既(ji)需(xu)較(jiao)多的建設資金,又(you)增加了系(xi)統的電(dian)(dian)(dian)力損耗。適當提高供(gong)電(dian)(dian)(dian)電(dian)(dian)(dian)壓,將原二次(ci)乃至(zhi)三次(ci)降壓減少為(wei)一次(ci),可大(da)大(da)減少供(gong)電(dian)(dian)(dian)系(xi)統的設備(bei)與線路(lu)損耗。

③布局不合理

許多地(di)區(qu)的(de)(de)(de)用(yong)電(dian)(dian)戶(hu)和(he)企業(ye)的(de)(de)(de)用(yong)電(dian)(dian)設備遠離配電(dian)(dian)中(zhong)心,使(shi)得低(di)(di)壓(ya)(ya)(0.4千伏)送電(dian)(dian)距離過(guo)長(chang),造成很大(da)(da)的(de)(de)(de)線路損(sun)耗和(he)電(dian)(dian)壓(ya)(ya)降落。這種情(qing)況在(zai)(zai)舊的(de)(de)(de)大(da)(da)、中(zhong)型企業(ye)中(zhong)普遍(bian)存在(zai)(zai),原因(yin)是(shi)當(dang)時設計規(gui)定配電(dian)(dian)中(zhong)心要建(jian)在(zai)(zai)企業(ye)的(de)(de)(de)引進電(dian)(dian)源的(de)(de)(de)一端。改善的(de)(de)(de)措施是(shi)在(zai)(zai)保證安全的(de)(de)(de)前提下,盡量移近配電(dian)(dian)中(zhong)心與用(yong)電(dian)(dian)設備的(de)(de)(de)距離,將原來(lai)低(di)(di)壓(ya)(ya)長(chang)距離送電(dian)(dian)改為高壓(ya)(ya)長(chang)距離、低(di)(di)壓(ya)(ya)短距離送電(dian)(dian),可以(yi)大(da)(da)大(da)(da)減少送電(dian)(dian)線路的(de)(de)(de)損(sun)耗。

④無功功率短缺

隨(sui)著經濟的(de)發展,供(gong)(gong)配(pei)(pei)電系統(tong)中感性負荷迅(xun)速增加,眾多的(de)配(pei)(pei)電變壓(ya)器(qi)和電動(dong)機(ji)處(chu)于(yu)低(di)負荷率(lv)(lv)(lv)(lv)的(de)非經濟運行狀態,造成供(gong)(gong)配(pei)(pei)電系統(tong)無功功率(lv)(lv)(lv)(lv)的(de)大量(liang)需求,如(ru)不及時(shi)補充,將引起供(gong)(gong)電電壓(ya)質量(liang)下降(jiang),系統(tong)損耗增加,既(ji)要(yao)浪費電能(neng),又將影響供(gong)(gong)配(pei)(pei)電設備的(de)使(shi)用率(lv)(lv)(lv)(lv),甚至(zhi)造成事故。解(jie)決以(yi)上問題的(de)技術(shu)措施是(shi)(shi)在供(gong)(gong)電方和用電方加裝(zhuang)補償電容,前(qian)者(zhe)稱集中補償,直接受(shou)(shou)益(yi)者(zhe)是(shi)(shi)供(gong)(gong)電部門,用戶的(de)效益(yi)來(lai)自少受(shou)(shou)功率(lv)(lv)(lv)(lv)因數(shu)不達標的(de)罰款;后者(zhe)稱為就地補償,直接受(shou)(shou)益(yi)者(zhe)是(shi)(shi)用戶,主(zhu)要(yao)是(shi)(shi)減少線(xian)路損耗。無功補償的(de)效益(yi)除上述之外(wai),還可以(yi)增大發電機(ji)、變壓(ya)器(qi)等設備的(de)利(li)用率(lv)(lv)(lv)(lv),降(jiang)低(di)供(gong)(gong)電成本,提高系統(tong)運行的(de)安全性。

⑤配電設備陳舊落后

我國在用(yong)的(de)(de)配電(dian)設備如(ru)配電(dian)變(bian)壓(ya)器(qi)及各類開關,許多是(shi)陳(chen)舊(jiu)(jiu)落后(hou)(hou)(hou)的(de)(de),由于資金(jin)不(bu)足和(he)相(xiang)關部(bu)門節能(neng)(neng)(neng)意識不(bu)夠等原因,不(bu)能(neng)(neng)(neng)及時更(geng)新(xin)(xin),結果浪費(fei)了大(da)量電(dian)能(neng)(neng)(neng)。如(ru)配電(dian)變(bian)壓(ya)器(qi)的(de)(de)空載損耗(hao)60年代(dai)(dai)初(chu)(chu)的(de)(de)ST型(xing)變(bian)壓(ya)器(qi)是(shi)70年代(dai)(dai)初(chu)(chu)期(qi)產(chan)品(pin)S1型(xing)變(bian)壓(ya)器(qi)的(de)(de)1.32倍,S1系(xi)列又比(bi)S6系(xi)列的(de)(de)大(da)約14%,而90年代(dai)(dai)后(hou)(hou)(hou)期(qi)以(yi)前應(ying)用(yong)的(de)(de)S7系(xi)列變(bian)壓(ya)器(qi)又比(bi)S6系(xi)列的(de)(de)小45%,90年代(dai)(dai)末國家(jia)推廣使用(yong)的(de)(de)S9系(xi)列變(bian)壓(ya)器(qi)的(de)(de)空載損耗(hao)和(he)負載損耗(hao)更(geng)小。其它如(ru)電(dian)磁(ci)開關、電(dian)纜接(jie)頭及連接(jie)金(jin)具等情形類似(si)。如(ru)能(neng)(neng)(neng)及時更(geng)新(xin)(xin)這些陳(chen)舊(jiu)(jiu)落后(hou)(hou)(hou)的(de)(de)配電(dian)設備,可(ke)使配電(dian)系(xi)統減少大(da)量無謂的(de)(de)電(dian)能(neng)(neng)(neng)浪費(fei)。



文(wen)章編輯:CobiNet(寧(ning)波),本公司專(zhuan)注于電訊配件,銅纜(lan)綜(zong)合布線系列(lie)領域產(chan)(chan)品研發生產(chan)(chan)超(chao)五(wu)類(lei),六類(lei),七類(lei)屏(ping)蔽網線/屏(ping)蔽模(mo)塊(kuai)及(ji)相(xiang)關模(mo)塊(kuai)配件,歡迎來電咨(zi)詢0574 88168918,網址aliance.cn